EVCO S.p.A. • Code 104KB62A123
EVKB62 and EVKB72 Controllers for normal temperature and low temperature refrigerated units with compressor protection against the electric system voltage fluctuations version 1.2
GB ENGLISH
1 GETTING STARTED
1.1 Important
Read these instructions carefully before installing and using the instru-
ment and follow all additional information for installation and electrical
connection; keep these instructions close to the instrument for future
consultations.
The instrument must be disposed according to the local
legislation about the collection for electrical and electronic
equipment.
1.2 Installing the instrument
Panel mounting, with click brackets (supplied by the builder); dimen-
sions in mm (in).
DIMENS. MINIMUM TYPICAL MAXIMUM
A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826)
B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)
Additional information for installation:
59.0 (2.322) is the maximum depth with screw terminal blocks
81.5 (3.208) is the maximum depth with extractable terminal blocks
the panel thickness must not be higher than 8.0 mm (0.314 in)
working conditions (working temperature, humidity, etc.) must be be-
tween the limits indicated in the technical data
do not install the instrument close to heating sources (heaters, hot air
ducts, etc.), devices provided with big magnetos (big speakers, etc.),
locations subject to direct sunlight, rain, humidity, dust, mechanical
vibrations or bumps
according to the safety legislation, the protection against electrical
parts must be ensured by a correct installation of the instrument; the
parts that ensure the protection must be installed so that you can not
remove them if not by using a tool.
1.3 Wiring diagram
With reference to the wiring diagrams:
the load managed by relay K2 depends on parameter u0
the serial port (by request) is the port for the communication with the
programming key.
Additional information for electrical connection:
do not operate on the terminal blocks with electrical or pneumatic
screwers
if the instrument has been moved from a cold location to a warm one,
the humidity could condense on the inside; wait about an hour be-
fore supplying it
test the working power supply voltage, working electrical frequency
and working electrical power of the instrument; they must correspond
with the local power supply
disconnect the local power supply before servicing the instrument
do not use the instrument as safety device
for repairs and information on the instrument please contact Evco
sales network.
2 USER INTERFACE
2.1 Preliminary information
There are the following operation status:
status “on” (the instrument is supplied and is turned on: the regulators
can be turned on)
status “stand-by” (the instrument is supplied but it is turned off via
software: the regulators are turned off)
status “off” (the instrument is not supplied).
“Turning on” means moving from status stand-by to status on; “turning
off” means moving from status on to status stand-by.
“turning the compressor on” or “starting the compressor up” means
activating the compressor relay
“turning the compressor off” means deactivating the compressor relay
“electric system voltage” means the effective value of the electric sys-
tem voltage.
After an interruption of power supply the instrument moves to the sta-
tus it was before the interruption.
The load managed by relay K2 depends on parameter u0, as follows:
if parameter u0 has value 0 (default value), the load will be the defrost
system (a heater for electric defrost or a valve for hot gas defrost)
if parameter u0 has value 1, the load will be the evaporator fan (the
defrost occurs stopping the compressor).
2.2 Turning on/off the instrument
make sure the keyboard is not locked and no procedure is running
press 4 s.
2.3 The display
If the instrument is turned on, during the normal operation the display
will show the cabinet temperature.
If the instrument is turned off, the display will be switched off.
2.4 Showing the electric system voltage
make sure the keyboard is not locked and no procedure is running
press 2 s: the display will show “Ui
press
To quit the procedure:
press or do not operate 60 s
press or or do not operate 60 s.
2.5 Showing the evaporator temperature
make sure the keyboard is not locked and no procedure is running
press 2 s: the display will show “P2
press
To quit the procedure:
press or do not operate 60 s
press or as long as the display shows the cabinet
temperature or do not operate 60 s.
If the evaporator probe is not enabled (parameter P3 = 0), the label
P2” will not be shown.
2.6 Activating the defrost by hand
make sure the keyboard is not locked and no procedure is running
press 4 s.
If the function of the evaporator probe is the one of defrost probe (pa-
rameter P3 = 1) and to the defrost activation the evaporator tempera-
ture is above the one you have set with parameter d2, the defrost will
not be activated.
2.7 Locking/unlocking the keyboard
To lock the keyboard:
make sure no procedure is running
press and 1 s: the display will show “Lo” 1 s.
If the keyboard is locked, you will not be allowed to:
show the power supply voltage
turn on/off the instrument through button
show the evaporator temperature
activate the defrost by hand
modify the working setpoint with the procedure related in paragraph
3.1 (you also can modify the working setpoint through parameter SP).
These operations provoke the visualization of the label “Lo” 1 s.
To unlock the keyboard:
press and 1 s: the display will show “Un” 1 s.
3 SETTINGS
3.1 Setting the working setpoint
make sure the keyboard is not locked and no procedure is running
press : LED will flash
press or in 15 s; also look at parameters r1 and r2
press or do not operate 15 s.
You also can modify the working setpoint through parameter SP.
3.2 Setting configuration parameters
To gain access the procedure (for the models without access password):
make sure the keyboard is not locked and no procedure is running
press and 4 s: the display will show “SP”.
To gain access the procedure (for the models with access password):
make sure no procedure is running
press and 4 s: the display will show “PA
press
press or in 15 s to set “-19
press or do not operate 15 s
press and 4 s: the display will show “SP”.
To select a parameter:
press or
To modify a parameter:
press
press or in 15
press or do not operate 15 s.
To quit the procedure:
press and 4 s or do not operate 60 s.
Switch off/on the power supply of the instrument after the
modification of the parameters.
4 SIGNALS
4.1 Signals
LED MEANING
LED compressor
if it is lit, the compressor will be turned on
if it flashes:
the modification of the working setpoint will be running
a compressor protection will be running (parameters C0,
C2, C4, C5 and C6)
LED defrost
if it is lit, the defrost will be running
if it flashes:
the defrost will be required but a compressor protection
will be running (parameters C0 and C2, only if parameter
u0 has value 0)
the dripping will be running (parameter d7)
the heating of the freezing fluid will be running (param-
eter dA, only if parameter u0 has value 0)
LED evaporator fan (only if parameter u0 has value 1)
if it is lit, the evaporator fan will be turned on
LED alarm
if it is lit, a compressor protection because of parameters C4,
C5 and C6, an alarm or an error will be running
°C LED Celsius degree
if it is lit, the unit of measure of the temperatures will be
Celsius degree (parameter P2)
°F LED Fahrenheit degree
if it is lit, the unit of measure of the temperatures will be
Fahrenheit degree (parameter P2)
CODE MEANING
CF Compressor forced start up
Remedies:
check the electric system voltage
look at parameter C8
Effects:
the instrument will make a compressor forced start up;
when the room temperature gets the working setpoint,
the instrument restore the normal display
Lo the keyboard is locked; look at paragraph 2.7
5 ALARMS
5.1 Alarms
CODE MEANING
AL Lower temperature alarm
Remedies:
check the cabinet temperature
look at parameter A1
Effects:
no effect
AH Upper temperature alarm
Remedies:
check the cabinet temperature
look at parameter A4
Effects:
no effect
iA Multipurpose input alarm (only if parameter i5 has value 1
or 2)
Remedies:
check the reasons that have provoked the activation of
the input
look at parameters i1 and i5
Effects:
if parameter i5 has value 1, there will be no effect
if parameter i5 has value 2, the compressor will be turned
off
id Door switch input alarm (only if parameter i5 has value 3 or
4)
Remedies:
check the reasons that have provoked the activation of
the input
look at parameters i1 and i5
Effects:
if parameter i5 has value 3, the compressor and the evapo-
rator fan will be turned off (this last only if parameter u0
has value 1)
if parameter i5 has value 4, the evaporator fan will be turned
off (only if parameter u0 has value 1)
UA Electric system voltage alarm
Remedies:
check the electric system voltage
look at parameters C4, C5 and C6
Effects:
the compressor will not be turned on or will be turned off
When the cause that has provoked the alarm disappears, the instru-
ment restores the normal operation.
6 INTERNAL DIAGNOSTICS
6.1 Internal diagnostics
CODE MEANING
P1 Cabinet probe error
Remedies:
check the kind of probe
check the integrity of the probe
check the connection instrument-probe
check the cabinet temperature
Effects:
the compressor will be turned on cyclically, 10 min turned
on and 10 min turned off
P2 Evaporator probe error
Remedies:
the same you saw in the previous case but related to the
evaporator probe
Effects:
if parameter P3 has value 1, the defrost will last the time
you will have set with parameter d3
if parameter F0 has value 1 or 2, the instrument will work
as if the parameter had value 0 (only if parameter u0 has
value 1)
When the cause that has provoked the alarm disappears, the instru-
ment restores the normal operation.
7 TECHNICAL DATA
7.1 Technical data
Box: self-extinguishing grey.
Frontal protection: IP 65.
Connections: screw terminal blocks (power supply, inputs and out-
puts), 6 poles connector (serial port; by request); extractable terminal
blocks (power supply, inputs and outputs) by request.
Working temperature: from 0 to 55 °C (32 to 131 °F, 10 ... 90% of
relative humidity without condensate).
Power supply: 230 VAC, 50/60 Hz, 3 VA (approximate).
Measure inputs: 2 (cabinet probe and evaporator probe) for
PTC or NTC probes (according to the model).
Digital inputs: 1 (multipurpose/door switch) for NO/NC contact (free
of voltage, 5 V 1 mA).
Working range: from -50 to 150 °C (-50 to 199 °F) for PTC probe,
from -40 to 105 °C (-40 to 199 °F) for NTC probe.
Resolution: 0.1 °C (between -19.9 and 19.9 °C)/1 °C/1 °F.
Digital outputs: 2 relays:
compressor relay: 16 res. A @ 250 VAC in
EVKB62 (NO contact); 30 res. A @ 250 VAC in
EVKB72 (NO contact)
defrost/evaporator fan relay: 8 res. A @
250 VAC (change-over contact).
The maximum current allowed on the loads is 10 A.
Serial port: port for the communication with the programming key;
by request.
I ITALIANO
1 PREPARATIVI
1.1 Importante
Leggere attentamente queste istruzioni prima dell’installazione e prima
dell’uso e seguire tutte le avvertenze per l’installazione e per il collega-
mento elettrico; conservare queste istruzioni con lo strumento per con-
sultazioni future.
Lo strumento deve essere smaltito secondo le normative
locali in merito alla raccolta delle apparecchiature elettriche
ed elettroniche.
1.2 Installazione
A pannello, con le staffe a scatto in dotazione (si vedano i disegni del
paragrafo 1.2 della sezione in Inglese).
Avvertenze per l’installazione:
59,0 è la profondità massima con morsettiere a vite
81,5 è la profondità massima con morsettiere estraibili
lo spessore del pannello non deve essere superiore a 8,0 mm
accertarsi che le condizioni di lavoro (temperatura di impiego, umidi-
tà, ecc.) rientrino nei limiti indicati nei dati tecnici
non installare lo strumento in prossimità di fonti di calore (resistenze,
condotti dell’aria calda, ecc.), di apparecchi con forti magneti (grossi
diffusori, ecc.), di luoghi soggetti alla luce solare diretta, pioggia, umi-
dità, polvere eccessiva, vibrazioni meccaniche o scosse
in conformità alle normative sulla sicurezza, la protezione contro even-
tuali contatti con le parti elettriche deve essere assicurata mediante
una corretta installazione dello strumento; tutte le parti che assicurano
la protezione devono essere fissate in modo tale da non poter essere
rimosse senza l’aiuto di un utensile.
1.3 Collegamento elettrico
Si vedano i disegni del paragrafo 1.3 della sezione in Inglese.
Con riferimento agli schemi elettrici:
l’utenza gestita dal relè K2 dipende dal parametro u0
la porta seriale (su richiesta) è la porta per la comunicazione con la
chiave di programmazione.
Avvertenze per il collegamento elettrico:
non operare sulle morsettiere utilizzando avvitatori elettrici o pneuma-
tici
se lo strumento è stato portato da un luogo freddo a uno caldo, l’umi-
dità potrebbe condensare all’interno; attendere circa un’ora prima di
alimentarlo
accertarsi che la tensione di alimentazione, la frequenza e la potenza
elettrica operativa dello strumento corrispondano a quelle dell’alimen-
tazione locale
disconnettere l’alimentazione prima di procedere con qualunque tipo
di manutenzione
non utilizzare lo strumento come dispositivo di sicurezza
per le riparazioni e per informazioni riguardanti lo strumento rivolgersi
alla rete di vendita Evco.
2 INTERFACCIA UTENTE
2.1 Cenni preliminari
Esistono i seguenti stati di funzionamento:
lo stato “on” (lo strumento è alimentato ed è acceso: i regolatori pos-
sono essere accesi)
lo stato “stand-by” (lo strumento è alimentato ma è spento via software:
i regolatori sono spenti)
lo stato “off” (lo strumento non è alimentato).
Con il termine “accensione” si intende il passaggio dallo stato stand-by
allo stato on; con il termine “spegnimento” si intende il passaggio dallo
stato on allo stato stand-by.
con il termine “accensione del compressore” si intende l’attivazione
del relè compressore
con il termine “spegnimento del compressore” si intende la
disattivazione del relè compressore
con il termine “tensione di rete” si intende il valore efficace della tensio-
ne di rete.
Dopo un’interruzione dell’alimentazione lo strumento passa allo stato in
cui si trovava prima dell’interruzione.
L’utenza gestita dal relè K2 dipende dal parametro u0, nel modo indica-
to:
se il parametro u0 è impostato a 0 (impostazione predefinita), l’utenza
sarà il sistema di sbrinamento (una resistenza in caso di sbrinamento
elettrico o una valvola in caso di sbrinamento a gas caldo)
se il parametro u0 è impostato a 1, l’utenza sarà il ventilatore
dell’evaporatore (lo sbrinamento avviene per fermata del compresso-
re).
2.2 Accensione/spegnimento dello strumento
assicurarsi che la tastiera non sia bloccata e che non sia in corso alcu-
na procedura
premere per 4 s.
2.3 Il display
Se lo strumento è acceso, durante il normale funzionamento il display
visualizzerà la temperatura della cella.
Se lo strumento è spento, il display sarà spento.
2.4 Visualizzazione della tensione di rete
assicurarsi che la tastiera non sia bloccata e che non sia in corso alcu-
na procedura
premere per 2 s: il display visualizzerà “Ui
premere
Per uscire dalla procedura:
premere o non operare per 60 s
premere o o non operare per 60 s.
2.5 Visualizzazione della temperatura dell’evaporatore
assicurarsi che la tastiera non sia bloccata e che non sia in corso alcu-
na procedura
premere per 2 s: il display visualizzerà “P2
premere
Per uscire dalla procedura:
premere o non operare per 60 s
premere o fino a quando il display visualizza la temperatura
della cella o non operare per 60 s.
Se la sonda evaporatore è assente (parametro P3 = 0), la label “P2” non
verrà visualizzata.
2.6 Attivazione dello sbrinamento in modo manuale
assicurarsi che la tastiera non sia bloccata e che non sia in corso alcu-
na procedura
premere per 4 s.
Se la funzione della sonda evaporatore è quella di sonda di sbrinamento
(parametro P3 = 1) e all’attivazione dello sbrinamento la temperatura
dell’evaporatore è al di sopra di quella stabilita con il parametro d2, lo
sbrinamento non verrà attivato.
2.7 Blocco/sblocco della tastiera
Per bloccare la tastiera:
assicurarsi che non sia in corso alcuna procedura
premere e per 1 s: il display visualizzerà “Lo” per 1 s.
Se la tastiera è bloccata, non sarà consentito:
visualizzare la tensione di rete
accendere/spegnere lo strumento attraverso il tasto
visualizzare la temperatura dell’evaporatore
attivare lo sbrinamento in modo manuale
modificare il setpoint di lavoro con la procedura indicata nel paragrafo
3.1 (il setpoint di lavoro è impostabile anche attraverso il parametro
SP).
Queste operazioni provocano la visualizzazione della label “Lo” per 1 s.
Per sbloccare la tastiera:
premere e per 1 s: il display visualizzerà “Un” per 1 s.
3 IMPOSTAZIONI
3.1 Impostazione del setpoint di lavoro
assicurarsi che la tastiera non sia bloccata e che non sia in corso alcu-
na procedura
premere : il LED lampeggerà
premere o entro 15 s; si vedano anche i parametri r1 e r2
premere o non operare per 15 s.
È inoltre possibile impostare il setpoint di lavoro attraverso il parametro
SP.
3.2 Impostazione dei parametri di configurazione
Per accedere alla procedura (per i modelli senza password di accesso):
assicurarsi che la tastiera non sia bloccata e che non sia in corso alcu-
na procedura
premere e per 4 s: il display visualizzerà “SP”.
Per accedere alla procedura (per i modelli con password di accesso):
assicurarsi che non sia in corso alcuna procedura
premere e per 4 s: il display visualizzerà “PA
premere
premere o entro 15 s per impostare “-19
premere o non operare per 15 s
premere e per 4 s: il display visualizzerà “SP”.
Per selezionare un parametro:
premere o
Per modificare un parametro:
premere
premere o entro 15 s
premere o non operare per 15 s.
Per uscire dalla procedura:
premere e per 4 s o non operare per 60 s.
Interrompere l'alimentazione dello strumento dopo la mo-
difica dei parametri.
4 SEGNALAZIONI
4.1 Segnalazioni
LED SIGNIFICATO
LED compressore
se è acceso, il compressore sarà acceso
se lampeggia:
sarà in corso la modifica del setpoint di lavoro
sarà in corso una protezione del compressore (parametri
C0, C2, C4, C5 e C6)
LED sbrinamento
se è acceso, sarà in corso lo sbrinamento
se lampeggia:
sarà richiesto lo sbrinamento ma sarà in corso una prote-
zione del compressore (parametri C0 e C2, solo se il para-
metro u0 è impostato a 0)
sarà in corso il gocciolamento (parametro d7)
sarà in corso il riscaldamento del fluido refrigerante (para-
metro dA, solo se il parametro u0 è impostato a 0)
LED ventilatore dell’evaporatore (solo se il parametro u0 è
impostato a 1)
se è acceso, il ventilatore dell’evaporatore sarà acceso
LED allarme
se è acceso, sarà in corso una protezione del compressore
per effetto dei parametri C4, C5 e C6, un allarme o un errore
°C LED grado Celsius
se è acceso, l’unità di misura delle temperature sarà il grado
Celsius (parametro P2)
°F LED grado Fahrenheit
se è acceso, l’unità di misura delle temperature sarà il grado
Fahrenheit (parametro P2)
CODICE SIGNIFICATO
CF Accensione forzata del compressore
Rimedi:
verificare la tensione di rete
si veda il parametro C8
Conseguenze:
lo strumento effettuerà un’accensione forzata del compres-
sore; quando la temperatura della cella raggiunge il
setpoint di lavoro, lo strumento ripristina la normale
visualizzazione
Lo la tastiera è bloccata; si veda il paragrafo 2.7
5 ALLARMI
5.1 Allarmi
CODICE SIGNIFICATO
AL Allarme di temperatura di minima
Rimedi:
verificare la temperatura della cella
si veda il parametro A1
Conseguenze:
lo strumento continuerà a funzionare regolarmente
AH Allarme di temperatura di massima
Rimedi:
verificare la temperatura della cella
si veda il parametro A4
Conseguenze:
lo strumento continuerà a funzionare regolarmente
iA Allarme ingresso multifunzione (solo se il parametro i5 è im-
postato a 1 o 2)
Rimedi:
verificare le cause che hanno provocato l’attivazione del-
l’ingresso
si vedano i parametri i1 e i5
Conseguenze:
se il parametro i5 è impostato a 1, lo strumento continue-
rà a funzionare regolarmente
se il parametro i5 è impostato a 2, il compressore verrà
spento