WORKING SETPOINT
Label Min. Max. U.m. Stand. Working setpoint
r1 r2 (*) 0 working setpoint
CONFIGURATION PARAMETERS
Label Min. Max. U.m. Stand. Password
PA -55 99 --- 0 password (§)
Label Min. Max. U.m. Stand. Measure inputs
/0 1 4 --- 1 kind of probe
/1 -55 +99 (*)/8 0 calibration (§)
/2 0 6 --- 3 digital filter
/8 0 1 --- 1 unit of measure
/A 0 1 --- 1 evaporator probe enabling
Label Min. Max. U.m. Stand. ON-OFF temperature regulator associated to the work-
ing setpoint and to the compressor output
r0 +1 +15 (*) +2 hysteresis (differential) (§)
r1 -55 +99 (*) -50 minimum working setpoint programmable
r2 -55 +99 (*) +50 maximum working setpoint programmable
Label Min. Max. U.m. Stand. Compressor output protection
C0 0 240 (**) 1 disabling time to the output activation from the instrument start
C1 0 240 (**) 5 disabling time to the output activation from the previous activation
C2 0 240 (**) 3 disabling time to the output activation from the previous deactiva-
tion
C4 0 1 --- 0 disabling time to the output activation and deactivation
C5 1 240 (**) 10 cycle time for the output activation during a cabinet probe failure
alarm
C6 0 100 % 50 percentage of the cycle time during which the output gets acti-
vated during a cabinet probe failure alarm
Label Min. Max. U.m. Stand. Defrost regulator
d0 0 99 (**) 8 defrost interval
d1 0 1 --- 1 kind of defrost
d2 -55 +99 (*) +2 defrost stopping setpoint
d3 1 99 (**) 15 defrost maximum length
d4 0 1 --- 0 defrost cycle at the instrument start
d5 0 99 (**) 0 delay to a defrost cycle activation from the instrument start
d6 0 1 --- 1 locking of the displayed temperature from a defrost cycle activation
d7 0 15 (**) 2 dripping length
d9 0 1 --- 0 disabling times to the compressor output activation override
dA --- --- (*) --- evaporator probe reading (§)
db 0 1 --- 0 times base
Label Min. Max. U.m. Stand. Alarm regulator
A0 +1 +15 (*) +2 hysteresis (differential)
A1 -55 0 (*) 0 lower temperature alarm set relative to the working setpoint
A2 0 +99 (*) 0 upper temperature alarm set relative to the working setpoint
A3 0 240 (**) 120 disabling time to the temperature alarm activation from the instru-
ment start
A5 -1 120 (**) 30 disabling time to the buzzer activation for the multifunction digital
input alarm indication
A6 0 240 (**) 5 disabling time to the temperature alarm activation
A7 0 240 (**) 15 disabling time to the temperature alarm activation from the defrost
cycle end
Label Min. Max. U.m. Stand. Evaporator fans regulator associated to the evaporator
fans output
F1 -55 +99 (*) -1 output deactivation setpoint
F2 +1 +15 (*) +2 hysteresis (differential)
F4 0 2 --- 0 output functioning during the defrost and the dripping
F5 0 15 (**) 2 evaporator fans stoppage length
F6 0 1 --- 0 kind of output deactivation setpoint
F7 0 4 --- 4 output functioning during the normal functioning
Label Min. Max. U.m. Stand. Digital inputs
i0 0 5 --- 4 action given during the multifunction digital input activation
i1 0 1 --- 0 kind of contact of the multifunction digital input
i2 0 2 --- 0 action given during the locking digital input activation (®)
i3 0 15 --- 0 number of locking digital inputs alarm enough to give the instru-
ment locking (®)
i4 0 240 (**) 0 time required to clear the locking digital inputs alarm counter (®)
i5 0 15 (**) 0 disabling time to the compressor output activation from the previ-
ous locking digital input deactivation (®)
Label Min. Max. U.m. Stand. User-output configuration
u1 0 6 --- 0 user to associate to the output K 1A (®)
u2 0 6 --- 1 user to associate to the output K 2A (®)
u3 0 6 --- 2 user to associate to the output K 4A (®)
u4 0 6 --- 3 user to associate to the output K 3A (®)
u5 0 6 --- 5 user to associate to the output K 5A
Label Min. Max. U.m. Stand. Connection in a serial network with EVCOBUS protocol
communication
L1 1 15 --- 1 instrument address
L2 0 7 --- 0 instrument group
L3 7 240 sec. 30 time-out link
L4 0 3 --- 1 baud rate
Label Min. Max. U.m. Stand. Connection in a serial network with EVCONET protocol
2 3