EVK802 Digital controller for quick coolers management version 1.04
E ENGLISH
1 PREPARATIONS
1.1 Important
Please read these instructions carefully prior to installation and use, and
follow all the precautions for installation and electrical connections;
keep these instructions with the device for future consultation.
1.2 Installation
Per panel, using the snap-on brackets supplied; the dimensions are
given in mm.
DIMENS. MINIMUM TYPICAL MAXIMUM
A 71,0 71,0 71,8
B 29,0 29,0 29,8
Recommendations for installation:
the maximum depth with screw terminal blocks is 59.0
the maximum depth with removable terminal blocks is 83.0
the panel thickness must not exceed 8,0 mm
ensure that the operating conditions (operating temperature, humid-
ity, etc.) are within the limits indicated in the technical data sheets
do not install the device near to any sources of heat (heating elements,
hot air conduits, etc.), equipment containing powerful magnets (large
diffusers, etc.), areas affected by direct sunlight, rain, humidity, exces-
sive dust, mechanical vibration or shock
in compliance with safety regulations, the device must be installed
correctly, and in such a way as to protect against any contact with
electrical parts; all safety devices must be fixed so that they cannot be
removed without the use of tools.
1.3 Electrical connections
With reference to the electrical circuit diagram:
the service controlled by relay K2 depends on parameter u0
the serial port (available on request) is the port used for communicat-
ing with the monitoring system (by means of a serial interface, via TTL,
using the MODBUS communication protocol) or with the program-
ming key; the port must not be used for both purposes simultane-
ously.
Points to note for connecting to the electricity supply
do not use electric or pneumatic screw-wrenches on the terminal
board
if the device has been moved from a cold to a warm environment,
condensation may have formed inside; please wait approx. one hour
prior to switching on
• ensure that the voltage, frequency and operational power of the device
are compatible with the local power supply
•disconnect the power prior to proceeding with any kind of mainte-
nance operation
do not use the device as a safety device
for repairs and any information relating to the device, contact the
Evco dealer network.
2 USER INTERFACE
2.1 Introductory information
The device has the following operational states:
"on" (the device is switched on and an operating cycle is running)
"stand-by" (the device is switched on but no operating cycle is run-
ning)
"off" (the device is not switched on).
If power is interrupted during a timed blast chilling operation, when
power is restored, chilling will continue from the time point at which
the interruption occurred (with a maximum error of 10 minutes).
If power is interrupted during a set-temperature blast chilling opera-
tion, when power is restored, chilling will start again from the begin-
ning.
If power is interrupted during a storage operation, when power is
restored the storage operation will be reset.
If power is interrupted while in "stand-by" mode, when power is re-
stored the device will be in the same state.
2.2 The display
In the "on" state, during normal operation, the display shows:
the amount of time remaining for a timed blast chilling operation, if
this is ongoing
the temperature measured by the pin probe if a set-temperature chill-
ing operation is ongoing
the temperature of the cabinet, if storage is ongoing.
In "stand-by" mode, during normal operation, the display shows the
temperature of the cabinet for ½ s every 3 s.
2.3 Defrosting and the evaporator fan
The service controlled by relay K2 depends on parameter u0:
if u0 = 0, the service controlled by relay K2 will be defrosting (electri-
cal defrosting; the evaporator fan is not controlled)
if u0 = 0, the service controlled by relay K2 will be defrosting (electri-
cal defrosting; the evaporator fan is not controlled):
- during blast chilling, operation of the evaporator fan depends on
parameter F0
- during storage, operation of the evaporator fan depends on param-
eter F2
- the evaporator fan is started during defrosting.
In "stand-by" mode it is only possible to activate manual defrosting; if
the service controlled by relay K2 is the evaporator fan (parameter u0
= 1), during defrosting the evaporator fan will be switched on, and
during drip-draining, this will be switched off.
To start defrosting in manual mode:
ensure no procedure is running
press for 4 s.
Defrosting is never activated during blast-chilling.
Defrosting occurs periodically during storage; it is possible to start
defrosting manually.
2.4 Viewing the status of the compressor and the evapora-
tor fan
To view the compressor status:
ensure no procedure is running
press : the display will show the first available label:
- if the display shows "C-1", the compressor will be switched-on
- if the display shows "C-0", the compressor will be switched off
- if the display shows "C-P", compressor protection will be ongoing
(parameters C0, C1, C2 and i7).
To view the status of the evaporator fan:
ensure no procedure is running
press twice: the display will show the first available label:
- if the display shows "F-1", the evaporator fan will be switched on
- if the display shows "F-0", the evaporator fan will be switched off
- if the display shows "F-P", then evaporator fan deferred activation will
be ongoing (parameter F8).
To exit the procedure:
press until the display shows the ongoing status value (see para-
graph 2.2), or leave for 15 s.
If the service controlled by relay K2 is defrosting (parameter u0 = 0),
labels "F-1", "F-0" and "F-P" will not be displayed.
2.5 Buzzer mute
ensure no procedure is running
press any key (the first key press does not trigger the associated effect).
3 OPERATIONAL CYCLES
3.1 Introductory information
The device has the following operational cycles:
timed positive chilling and storage
timed negative chilling and storage
set-temperature positive chilling and storage
set-temperature negative chilling and storage.
Set-temperature cycles are preceded by a test step in order to check
correct insertion of the pin probe (see paragraph 3.6).
To re-start using the same settings as the last cycle run:
ensure that the device is in "stand-by" mode, that no procedures are
running and that another cycle has not been selected
press 2 s: the display will show the label of the last cycle run
press within 60 s: in the case of a timed cycle, the display will
show the duration of the blast chilling step (in minutes) or
in the case of a set-temperature cycle, the set target tempera-
ture
press or within 15 s to change the value (the setting re-
mains active until another cycle is selected, when the value
r1, r2, r3 or r4 is restored)
press within 15 s: the cycle will be activated.
3.2 Timed positive blast chilling and storage cycle
To start the cycle:
ensure the device is in "stand-by" mode and no procedures are run-
ning
press to select "PoS" and ensure the LED is flashing
press within 15 s: the display will show the duration of the blast
chilling step (in minutes)
press or within 15 s to change the value (the setting re-
mains active until another cycle is selected, when the value
assigned by parameter r1 is restored)
press : the display will show the chilling operational setpoint (in
°C/°F) and the LED will flash
press or within 15 s to change the value (the setting re-
mains active until another cycle is selected, when the value
assigned by parameter r7 is restored)
press within 15 s: the cycle will be activated.
Also look at parameters rb and E0.
During chilling:
the display shows the residual chilling time remaining
the LED is on
parameter r1 sets the chilling time duration
parameter r7 sets the operational setpoint
press several times to:
- display the message "PoS"
- display the cabinet temperature
- exit the procedure, or leave for 15 s.
Once the chilling period has elapsed:
the device switches to storage mode
the display shows the message "End"
the buzzer sounds for the period of time set by parameter AA
• press any key to mute the buzzer; press once more to cancel the message
"End".
During storage:
the display shows the cabinet temperature
the LEDs and are on
the parameter r9 sets the operational setpoint
press several times to:
- display the message "PoS"
- exit the procedure, or leave for 15 s.
To interrupt the cycle:
press for 2 s.
3.3 Timed negative chilling and storage cycle
To start the cycle:
ensure the device is in "stand-by" mode and no procedures are run-
ning
press to select "nEg" and ensure the LED is flashing
press within 15 s: the display will show the duration of the blast
chilling step (in minutes)
press or within 15 s to change the value (the setting re-
mains active until another cycle is selected, when the value
assigned by parameter r2 is restored)
press : the display will show the chilling operational setpoint (in
°C/°F) and the LED will flash
press or within 15 s to change the value (the setting re-
mains active until another cycle is selected, when the value
assigned by parameter r8 is restored)
press within 15 s: the cycle will be activated.
Also look at parameters rb and E0.
During chilling:
the display shows the residual chilling time remaining
the LED is on
parameter r2 sets the chilling time duration
parameter r8 sets the operational setpoint
press several times to:
- display the message "nEg"
- display the cabinet temperature
- exit the procedure, or leave for 15 s.
Once the chilling period has elapsed:
the device switches to storage mode
the display shows the message "End"
the buzzer sounds for the period of time set by parameter AA
• press any key to mute the buzzer; press once more to cancel the message
"End".
During storage:
the display shows the cabinet temperature
the LEDs and are on
the parameter rA sets the operational setpoint
press several times to:
- display the message "nEg"
- exit the procedure, or leave for 15 s.
To interrupt the cycle:
press for 2 s.
3.4 Set-temperature positive blast chilling and storage cy-
cle
To start the cycle:
ensure the device is in "stand-by" mode and no procedures are run-
ning
press to select "PoS" and ensure the LED is flashing
press within 15 s: the display will show the blast chilling end-
point temperature
press or within 15 s to change the value (the setting re-
mains active until another cycle is selected, when the value
assigned by parameter r3 is reset)
press : the display will show the chilling operational setpoint (in
°C/°F) and the LED will flash
press or within 15 s to change the value (the setting re-
mains active until another cycle is selected, when the value
assigned by parameter r7 is restored)
press within 15 s: the cycle will be activated.
Also look at parameters rb and E0.
Prior to starting the cycle:
the test is run in order to check correct pin probe insertion (see para-
graph 3.6):
- if the outcome of the test is positive, the cycle will be started
- if the outcome of the test is negative, the cycle will be started in timed
mode.
During chilling:
the display shows the temperature measured by the pin probe
the LED is on
the parameter r3 sets the blast chilling endpoint temperature
the parameter r5 sets the maximum chilling time duration
the parameter r7 sets the operational setpoint
press several times to:
- display the maximum residual chilling time remaining
- display the message "PoS"
- display the flashing cabinet temperature
- exit the procedure, or leave for 15 s.
If the temperature measured by the pin probe reaches the chilling
endpoint temperature prior to expiry of the maximum chilling time
duration:
the device will switch to storage mode
the display will show the message "End"
the buzzer will sound for the period of time set by parameter AA
press any key to mute the buzzer; press once more to cancel the
message "End".
If the temperature measured by the pin probe does not reach the chill-
ing endpoint temperature prior to expiry of the maximum chilling time
duration:
chilling will continue
the LED will flash and the LED will be on
the buzzer will sound
press several times to:
- mute the buzzer
- display the time elapsed since the maximum chilling time expired
- display the cabinet temperature
- display the message "PoS"
- exit the procedure, or leave for 15 s
when the temperature measured by the pin probe reaches the chill-
ing endpoint temperature:
- the device switches to storage mode
- the LED will continue to flash and the LED will stay on
- the display will show the message "End"
- the buzzer will sound for the period of time set by parameter AA
- press any key to mute the buzzer; press once more to cancel the
message "End".
During storage:
the display shows the cabinet temperature
if chilling had a positive outcome, the LEDs and and will be
on; if chilling had a negative outcome, the LEDs and will be
on and the LED will flash
the parameter r9 sets the operational setpoint
press several times to:
- display the message "PoS"
- exit the procedure, or leave for 15 s.
To interrupt the cycle:
press for2 s.
3.5 Set-temperature negative chilling and storage cycle
To start the cycle:
ensure the device is in "stand-by" mode and no procedures are run-
ning
press to select "nEg" and ensure the LED is flashing
press within 15 s: the display will show the blast chilling end-
point temperature
press or within 15 s to change the value (the setting re-
mains active until another cycle is selected, when the value
assigned by parameter r4 is restored)
press : the display will show the chilling operational setpoint (in
°C/°F) and the LED will flash
press or within 15 s to change the value (the setting re-
mains active until another cycle is selected, when the value
assigned by parameter r8 is restored)
press within 15 s: the cycle will be activated.
Also look at parameters rb and E0.
Prior to starting the cycle:
the test is run in order to check correct pin probe insertion (see para-
graph 3.6):
- if the outcome of the test is positive, the cycle will be started
- if the outcome of the test is positive, the cycle will be started.
During chilling:
the display shows the temperature measured by the pin probe
the LED is on
the parameter r4 sets the chilling endpoint temperature
the parameter r6 sets the maximum chilling time duration
the parameter r8 sets the operational setpoint
press several times to:
- display the maximum residual chilling time remaining
- display the message "nEg"
- flashing display the cabinet temperature
- exit the procedure, or leave for 15 s.
If the temperature measured by the pin probe reaches the chilling
endpoint temperature prior to expiry of the maximum chilling time
duration:
the device will switch to storage mode
the display will show the message "End"
the buzzer will sound for the period of time set by parameter AA
press any key to mute the buzzer; press once more to cancel the
message "End".
If the temperature measured by the pin probe does not reach the chill-
ing endpoint temperature prior to expiry of the maximum chilling time
duration:
chilling will continue
the LED will flash and the LED will be on
the buzzer will sound
press several times to:
- mute the buzzer
- display the time elapsed since the maximum chilling time expired
- display the cabinet temperature
- display the message "nEg"
- exit the procedure, or leave for 15 s
when the temperature measured by the pin probe reaches the chill-
ing endpoint temperature:
- the device will switch to storage mode
- the LED will continue to flash and the LED will continue to
stay on
- the display will show the message "End"
- the buzzer will sound for the period of time set by parameter AA
- press any key to mute the buzzer; press once more to cancel the
message "End".
During storage:
the display shows the cabinet temperature
if chilling had a positive outcome, the LEDs and and will be
on; if chilling had a negative outcome, the LEDs and will be
on and the LED will flash
the parameter rA sets the operational setpoint
press several times to:
- display the message "nEg"
- exit the procedure, or leave for 15 s.
To interrupt the cycle:
press for2 s.
3.6 Test to check correct pin probe insertion
Set-temperature cycles are preceded by a test step in order to check
correct pin probe insertion.
The test has two stages:
if the outcome of the first stage is positive, the second will not be run
if the outcome of the first stage is negative, the second will be run.
The outcome of the first stage is positive if "the temperature measured
by the pin probe - the temperature of the cabinet" is greater than the
value set by parameter rc at least 3 times out of 5 (the comparison is
made every 10 s); if parameter rc is set to 0, neither the first nor second
stages will be run.
The outcome of the second stage is positive if the difference "tempera-
ture measured by the pin probe - temperature of the cabinet" is greater
by at least 1ºC/1ºF (with respect to the previous comparison) at least 6
times out of 8 (the comparison is made every "rd/8 s").
If the outcome of the test is positive:
the cycle will be activated.
the cycle will be activated:
the cycle will be started in timed mode
the LED will flash.
If power is interrupted during the test, when power is restored, the test
will start again from the beginning.
4 SETTINGS
4.1 Temporary setting of operational setpoint during stor-
age
ensure the device is in "stand-by" mode and no procedures are run-
ning
press : the LED will flash
press or within15 s
press or leave for 15 s.
The setting remains active until another operational cycle is selected,
when the value assigned by parameter r9 or ra is restored.
4.2 Setting the configuration parameters
The parameters are arranged on two levels.
To access the first level:
ensure the device is in "stand-by" mode and no procedures are run-
ning
press and for 4 s: the display will show “PA
To access the second level:
access the first level
press or to select “PA
press
press or within 15 s to set “-19
press or leave for 15 s
press and for4 s: the display will show “CA1”.
To select a parameter:
press or
To modify a parameter:
press
press or within 15 s
press or leave for 15 s.
To exit the procedure:
press and for 4 s, or leave for 60 s.
IInterrupt the device power supply after altering the param-
eters.
4.3 Resetting configuration parameter default values
ensure the device is in "stand-by" mode and no procedures are run-
ning
press and for 4 s: the display will show “PA
press
press or within 15 s to set “743
press or leave for 15 s
press and per 4 s: the display will show “dEF
press
press or within 15 s to set “149
press or leave for 15 s: the display will flash "dEF" for 4 s, after
which the device will exit the procedure
interrupt the power to the device.
Ensure that the parameter default values are appropriate,
particularly if the probes are NTC type.
5 SIGNALS
5.1 Signals
LED MESSAGE
timed chilling LED
if on and the LED is off, a timed chilling operation is
ongoing
if on and the LED is also on, a post timed-chilling stor-
age operation is ongoing
if flashing, a timed chilling and storage cycle will have
been selected
set-temperature chilling LED
if on and the LED is off, a set-temperature chilling op-
eration is ongoing
if on and the LED is also on, a post set-temperature
chilling storage operation will be ongoing
if flashing, a set-temperature chilling and storage cycle
will have been selected
if it is on for ½ s every 3 s, the test to verify correct pin probe
insertion will be ongoing
if flashing, and the LED is on, then the test to verify
correct pin probe insertion will have had a negative out-
come (parameters rc and rd) and the cycle will have been
started in timed mode; see paragraph 3.6
if flashing, and the LED is on, the chilling stage will
have had a negative outcome, and so this will continue
if flashing, and the LEDs and are on, the chilling
stage will have had a negative outcome, the device will
have switched to storage mode and this will be ongoing
storage LED
if on, a storage operation will be ongoing
if flashing, then the operational setpoint will be being
modified while a storage operation is ongoing (see para-
graph 4.1)
alarm LED
if on, an alarm is ongoing
°C degree Celsius LED
if on, the unit of measurement for temperature is degrees
Celsius (parameter P2)
°F degree Fahrenheit LED
if on, the unit of measurement for temperature is degrees
Fahrenheit (parameter P2)
decimal minute LED
point if flashing, the unit of measurement of magnitude displayed
is the minute
CODE MESSAGE
- d - defrosting or drip draining is ongoing