EVK711/EVK712 Single output/two outputs digital timers version 1.04
GB ENGLISH
1 GETTING STARTED
1.1 Important
Read these instructions carefully before installing and using the instru-
ment and follow all additional information for installation and electrical
connection; keep these instructions close to the instrument for future
consultations.
1.2 Installing the instrument
Panel mounting, with click brackets (supplied by the builder); dimen-
sions in mm (in).
DIMENS. MINIMUM TYPICAL MAXIMUM
A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826)
B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)
Additional information for installation:
59.0 (2.322) is the maximum depth with screw terminal blocks
83.0 (3.267) is the maximum depth with extractable terminal blocks
the panel thickness must not be higher than 8.0 mm (0.314 in)
working conditions (working temperature, humidity, etc.) must be be-
tween the limits indicated in the technical data
do not install the instrument close to heating sources (heaters, hot air
ducts, etc.), devices provided with big magnetos (big speakers, etc.),
locations subject to direct sunlight, rain, humidity, dust, mechanical
vibrations or bumps
according to the safety legislation, the protection against electrical
parts must be ensured by a correct installation of the instrument; the
parts that ensure the protection must be installed so that you can not
remove them if not by using a tool.
1.3 Wiring diagram
With reference to the wiring diagrams:
the serial port (by request) is the port for the communication with the
supervision system (through a serial interface, via TTL, with MODBUS
communication protocol) or with the programming key; the port must
not be used at the same time for the same purposes.
Additional information for electrical connection:
do not operate on the terminal blocks with electrical or pneumatic
screwers
if the instrument has been moved from a cold location to a warm one,
the humidity could condense on the inside; wait about an hour be-
fore supplying it
test the working power supply voltage, working electrical frequency
and working electrical power of the instrument; they must correspond
with the local power supply
disconnect the local power supply before servicing the instrument
do not use the instrument as safety device
for repairs and information on the instrument please contact Evco
sales network.
2 USER INTERFACE
2.1 Turning on/off the instrument
To turn on the instrument you have to supply it; to turn it off it is enough
to cut off the power supply.
If a lack of power supply arises when the count is running, the opera-
tion of the instrument to the restoration of the power supply will de-
pend on parameter t26.
2.2 Starting the count
make sure no procedure is running
provoke the effect you have set with parameter t11:
- if t11 = 0, press or activate input start
- if t11 = 1, press
- if t11 = 2, activate input start.
2.3 Stopping the count
make sure parameter t17 has value 0
provoke the effect you have set with parameter t12:
- if t12 = 0, press or activate input stop
- if t12 = 1, press
- if t12 = 2, activate input stop.
Otherwise:
press 4 s.
2.4 Suspending/resuming the count
To suspend the count:
make sure parameter t17 has value 2
provoke the effect you have set with parameter t12:
- if t12 = 0, press or activate input stop
- if t12 = 1, press
- if t12 = 2, activate input stop.
If the count is suspended when load 1 (or load 2) is turned on, the load
status during the suspension will depend on parameter t24 (or t25):
- if t24 (or t25) = 0, the load will be turned off
- if t24 (or t25) = 1, the load will remain turned on.
To resume the count:
provoke the effect you have set with parameter t11:
- if t11 = 0, press or activate input start
- if t11 = 1, press
- if t11 = 2, activate input start.
2.5 The display
If the count is running, the display will show the kind of count you have
set with parameter t15:
if t15 = 0, the display will show the remaining time (count down)
if t15 = 0, the display will show the elapsed time (count up).
If the count is suspended, the display will flash.
2.6 Silencing the buzzer in alarm
press a button (the first pressure of the button does not provoke its
usual effect).
3 OPERATION
3.1 Preliminary information
The operation mainly depends on the instrument code.
3.2 Operation with instrument code = 1
3.3 Operation with instrument code = 2
If the cyclical operation is not active (parameter t18 = 0), parameter t2
will not be visible.
3.4 Operation with instrument code = 3
To start the count:
make sure parameter t11 has value 0 or 2
activate input start.
To stop the count:
press 4 s.
If the duration of the activation of input start is shorter than the time
you have set with parameter t1, load 1 and the buzzer will not be turned
on.
3.5 Operation with instrument code = 4
During the activation of load 1:
the count is not shown
if you try to suspend the count, you will stop it.
3.6 Operation with instrument code = 5 (only EVK712)
If the cyclical operation is not active (parameter t18 = 0), parameter t3
will not be visible.
3.7 Operation with instrument code = 6 (only EVK712)
3.8 Operation with instrument code = 7 (only EVK712)
3.9 Operation with instrument code = 8 (only EVK712)
If the cyclical operation is not active (parameter t18 = 0), parameter t4
will not be visible.
3.10 Operation with instrument code = 9 (only EVK712)
During the activation of load 2:
the count is not shown
if you try to suspend the count, you will stop it.
4 SETTINGS
4.1 Setting the instrument code
To gain access the procedure:
make sure no count is running and no procedure is running
press and 4 s: the display will show “PA
press
press or in 15 s to set “743
press or do not operate 15 s
press and 4 s: the display will show “dEF
press
press or in 15 s to set “149
press or do not operate 15 s: the display will show “CFG”.
To modify the instrument code:
press
press or in 15 s
press or do not operate 15 s: the display will show “CFG” flash-
ing 4 s, after which the instrument will quit the procedure
switch off/on the power supply of the instrument.
To quit the procedure early:
press and 4 s or do not operate 60 s.
The modification of the instrument code provokes the res-
toration of the default value of configuration parameters;
to modify the instrument code provoking only the cancel-
lation of the value of parameters t1, t2, t3, t4 and t19,
modify parameter CFG with the procedure related in para-
graph 4.2.
4.2 Setting configuration parameters
Configuration parameters are arranged on two levels.
To gain access the first level:
make sure no count is running and no procedure is running
press and 4 s: the display will show “PA
To select a parameter:
press or
To modify a parameter:
press
press or in 15
press or do not operate 15 s.
To gain access the second level:
gain access the first level
press or to select “PA
press
press or in 15 s to set “-19
press or do not operate 15 s
press and 4 s: the display will show “t1”.
To quit the procedure:
press and 4 s or do not operate 60 s.
Switch off/on the power supply of the instrument after the
modification of the parameters.
4.3 Setting parameters t1, t2, t3 and t4 quickly
To modify parameter t1:
make sure no count is running and no procedure is running
press : LED will flash
press or in 15 s; also look at parameter t20.
To modify parameter t2 (if provided):
press in 15 s: LED will flash
press or in 15 s; also look at parameter t21.
To modify parameter t3 (if provided):
press in 15 s: LED will flash
press or in 15 s; also look at parameter t22.
To modify parameter t4 (if provided):
press in 15 s: LED will flash
press or in 15 s; also look at parameter t23
press or do not operate 15 s: the instrum. will quit the procedure.
To quit the procedure early:
do not operate 15 s.
5 SIGNALS
5.1 Signals
LED MEANING
out 1 LED load 1
if it is lit, load 1 will be turned on
out 2 LED load 2 (only EVK712)
if it is lit, load 2 will be turned on
LED time t1
if it is lit, the count of the time you have set with parameter
t1 will be running
if it flashes, the modification of parameter t1 will be running
(with the procedure indicated in paragraph 4.3)
LED time t2
if it is lit, the count of the time you have set with parameter
t2 will be running
if it flashes, the modification of parameter t2 will be running
(with the procedure indicated in paragraph 4.3)
LED time t3
if it is lit, the count of the time you have set with parameter
t3 will be running
if it flashes, the modification of parameter t3 will be running
(with the procedure indicated in paragraph 4.3)
LED time t4
if it is lit, the count of the time you have set with parameter
t4 will be running
if it flashes, the modification of parameter t4 will be running
(with the procedure indicated in paragraph 4.3)
h:m LED hours:minutes
if it is lit, the times base of the count that will be running will
be hours:minutes
m:s LED minutes:seconds
if it is lit, the times base of the count that will be running will
be minutes:seconds
6 ALARMS
6.1 Alarms
CODE MEANING
display Lack of power supply during the count
flashing Remedies:
check the reasons that have provoked the lack of power
supply
Effects:
the effect you have set with parameter t26
7 TECHNICAL DATA
7.1 Technical data
Box: self-extinguishing grey.
Frontal protection: IP 65.
Connections (use copper conductors only): screw terminal blocks
(power supply, inputs and outputs), 6 poles connector (serial port; by
request); extractable terminal blocks (power supply, inputs and outputs)
by request.
Working temperature: from 0 to 55 °C (32 to 131 °F, 10 ... 90% of
relative humidity without condensate).
Power supply: 230 VAC, 50/60 Hz, 3 VA (approximate); 115 VAC or
12-24 VAC/DC or 12 VAC/DC by request.
Insulation class: 2.
Alarm buzzer: incorporated.
Digital inputs: 2 (start and stop) for NO/NC contact (free of voltage,
5 V 1 mA).
Working range: from 1 ds to 99 h and 59 min.
Digital outputs EVK711: 1 relay:
load 1 relay: 8 res. A @ 250 VAC,
2 FLA, 12 LRA (change-over contact).
Digital outputs EVK712: 2 relays:
load 1 relay: 8 res. A @ 250 VAC,
2 FLA, 12 LRA (change-over contact)
load 2 relay: 8 res. A @ 250 VAC,
2 FLA, 12 LRA (change-over contact).
Serial port: port for the communication with the supervision system
(through a serial interface, via TTL, with MODBUS communication pro-
tocol) or with the programming key; by request.
I ITALIANO
1 PREPARATIVI
1.1 Importante
Leggere attentamente queste istruzioni prima dell’installazione e prima
dell’uso e seguire tutte le avvertenze per l’installazione e per il collega-
mento elettrico; conservare queste istruzioni con lo strumento per con-
sultazioni future.
1.2 Installazione
A pannello, con le staffe a scatto in dotazione (si vedano i disegni del
paragrafo 1.2 della sezione in Inglese).
Avvertenze per l’installazione:
59,0 è la profondità massima con morsettiere a vite
83,0 è la profondità massima con morsettiere estraibili
lo spessore del pannello non deve essere superiore a 8,0 mm
accertarsi che le condizioni di lavoro (temperatura di impiego, umidi-
tà, ecc.) rientrino nei limiti indicati nei dati tecnici
non installare lo strumento in prossimità di fonti di calore (resistenze,
condotti dell’aria calda, ecc.), di apparecchi con forti magneti (grossi
diffusori, ecc.), di luoghi soggetti alla luce solare diretta, pioggia, umi-
dità, polvere eccessiva, vibrazioni meccaniche o scosse
in conformità alle normative sulla sicurezza, la protezione contro even-
tuali contatti con le parti elettriche deve essere assicurata mediante
una corretta installazione dello strumento; tutte le parti che assicurano
la protezione devono essere fissate in modo tale da non poter essere
rimosse senza l’aiuto di un utensile.
1.3 Collegamento elettrico
Si vedano i disegni del paragrafo 1.3 della sezione in Inglese.
Con riferimento agli schemi elettrici:
la porta seriale (su richiesta) è la porta per la comunicazione con il
sistema di supervisione (attraverso un’interfaccia seriale, via TTL, con
protocollo di comunicazione MODBUS) o con la chiave di program-
mazione; la porta non deve essere utilizzata contemporaneamente
per i due scopi.
Avvertenze per il collegamento elettrico:
non operare sulle morsettiere utilizzando avvitatori elettrici o pneuma-
tici
se lo strumento è stato portato da un luogo freddo a uno caldo, l’umi-
dità potrebbe condensare all’interno; attendere circa un’ora prima di
alimentarlo
accertarsi che la tensione di alimentazione, la frequenza e la potenza
elettrica operativa dello strumento corrispondano a quelle dell’alimen-
tazione locale
disconnettere l’alimentazione prima di procedere con qualunque tipo
di manutenzione
non utilizzare lo strumento come dispositivo di sicurezza
per le riparazioni e per informazioni riguardanti lo strumento rivolgersi
alla rete di vendita Evco.
2 INTERFACCIA UTENTE
2.1 Accensione/spegnimento dello strumento
Per accendere lo strumento è necessario alimentarlo; per spegnerlo basta
togliere l’alimentazione.
Se si manifesta un’interruzione dell’alimentazione quando il conteggio
è in corso, il funzionamento dello strumento al ripristino dell’alimenta-
zione dipenderà dal parametro t26.
2.2 Avvio del conteggio
assicurarsi che non sia in corso alcuna procedura
provocare l’evento stabilito con il parametro t11:
- se t11 = 0, premere o attivare l’ingresso start
- se t11 = 1, premere
- se t11 = 2, attivare l’ingresso start.
2.3 Interruzione del conteggio
assicurarsi che il parametro t17 sia impostato a 0
provocare l’evento stabilito con il parametro t12:
- se t12 = 0, premere o attivare l’ingresso stop
- se t12 = 1, premere
- se t12 = 2, attivare l’ingresso stop.
In alternativa:
premere per 4 s.
2.4 Sospensione/ripresa del conteggio
Per sospendere il conteggio:
assicurarsi che il parametro t17 sia impostato a 2
provocare l’evento stabilito con il parametro t12:
- se t12 = 0, premere o attivare l’ingresso stop
- se t12 = 1, premere
- se t12 = 2, attivare l’ingresso stop.
Se il conteggio viene sospeso quando il carico 1 (o il carico 2) è acceso,
lo stato del carico durante la sospensione dipenderà dal parametro t24
(o t25):
se t24 (o t25) = 0, il carico verrà spento
se t24 (o t25) = 1, il carico rimarrà acceso.
Per riprendere il conteggio:
provocare l’evento stabilito con il parametro t11:
- se t11 = 0, premere o attivare l’ingresso start
- se t11 = 1, premere
- se t11 = 2, attivare l’ingresso start.
2.5 Il display
Se il conteggio è in corso, il display visualizzerà il tipo di conteggio stabi-
lito con il parametro t15:
se t15 = 0, il display visualizzerà il tempo residuo (count down)
se t15 = 1, il display visualizzerà il tempo trascorso (count up).
Se il conteggio è sospeso, il display lampeggerà.
2.6 Tacitazione buzzer in allarme
premere un tasto (la prima pressione del tasto non provoca l’effetto
associato).