C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 55
6.4.3 Protection timings
Below, there is a list of all the timings related to the management of the compressors.
Neutral Zone Timings
These parameters serve to adjust the time intervals of the requests for turn-on and shutdown of the various steps
supplied by the compressors:
Minimum time request for turn-ons
Maximum time request for turn-ons
Minimum time request for shutdowns
Maximum time request for shutdowns
For these parameters, refer to the description in paragraph 2.2.2.
Protection timings
These times serve to protect the mechanical instruments from the various breakaways to which they are
subjected.
PC04 Minimum time turn-on of compressors. Once activated, the compressor will stay on for this amount of
time before it can be shut off.
PC05 Minimum time shutdown of compressors. Minimum amount of time that must pass after the last
shutdown before the compressor can be turned on again.
PC06 Minimum time between turn-ons of same compressor. Establishes the minimum amount of time that
must pass between two turn-ons of the same compressor.
PC07 Minimum time between turn-ons of different compressors. Establishes the minimum amount of time
that must pass between the turn-on of one compressor and the next. If enabled, this serves to avoid
simultaneous breakaways.
PC08 Minimum time between shutdowns of different compressors. Establishes the minimum amount of time
that must pass between the shutdown of one compressor and the next.
PC09 Minimum time turn-on of throttlings. Establishes the minimum amount of turn-on time between the
throttlings of a compressor.
PC10 – Minimum time shutdown of throttlings. Establishes the minimum amount of shutdown time between the
throttlings of a compressor.
PC27 (PC47) speedUp time. If adjustment with inverter is set, this parameter, if different from zero, allows
the inverter output to remain at maximum level (100.00%) at each request for the turn-on of a new step.
6.4.4 Safety inputs
The program foresees the management of 1 safety “thermal compressor” input for each compressor. For this
input, it is possible to set the type of reset (automatic or manual) and the intervention delay, through the use of
parameters.
To enable the alarms related to these safety measures, besides setting the parameters mentioned above as
needed, it is also necessary to set the positions in which the digital inputs will be connected relative to the
various types of alarm from the menu Constructor -> Hardware. In the case where there is no wish to set the
alarm, all that is needed is to set the parameter mentioned above to the value of 0.